EDC SERIES

CONTACT YOUR SERVICE DEPARTMENT FOR ASSISTANCE OR SMART POWER SYSTEMS TECH SUPPORT – 800-772-7633

BASIC OPERATION


Setup – There are 8 UPS items that can be Set Up by the user.

  1. Press and hold the “ENTER” button for 5 seconds to activate the setting mode. The first configuration parameter will be displayed on the LCD screen.

Note: The manual settings programming mode can ONLY be invoked while UPS is in Bypass mode or Standby mode. To make UPS on Standby mode or Bypass mode, connect utility power to UPS and do not turn on UPS.

  1. Press the “ENTER” button to select the setting you want to configure.
  2. Press the “ESC” buttons to scroll through the different parameters and select the parameter you want.
  3. Press the “ESC” button for 5 seconds to cancel and exit setting mode. Press the “ENTER” button for 5 seconds to save all the settings you just do and exit setting mode.

SETTING ITEM


001


002


003


004


005


006


007


008

CONFIGURE SUBMENU


Output Voltage


Output Frequency


ECO Mode


Bypass Mode


Converter Mode


Site Fault


Bypass when UPS is Off


Outlet Group

AVAILABLE SETTINGS


[100V] [110V] [115V] [120V] [127V]


[50Hz] [60Hz]


[0%] (Disable) [10%][15%] (Enable)


[DIS] (Disable) [ENA] (Enable)


[DIS] (Disable) [ENA] (Enable)


[DIS] (Disable) [ENA] (Enable)


[FId] (Disable) [FIE] (Enable)


[DIS] (Disable) [ENA] (Enable)

DEFAULT SETTING


120V


60Hz


0%


Enable


Disable


Disable


Disable


Enable

*) When operating in ECO Mode, the efficiency of UPS is higher than that in online mode, but transfer time should not be 0ms.
**) When operating in Converter Mode, the frequency of output should be always 50Hz or 60Hz, but load capacity will be derated by 45%.
*) This function would be set as 0% when Converter Mode is enabled.
**) UPS has no bypass when Converter Mode is enabled.

EVENT CODE LIST

EVENT ID – DESCRIPTION OF CAUSE

E11 Bat Volt High:The external battery module connection is wrong, or the charger failed.


E12 Bat Volt Low: Batteries failed.


E14 Over Load: UPS is overloaded.


E18 Fan Fail: The ventilation hole has been covered, or the fans can’t work.


E19 Over Temperature: High ambient temperature, or the ventilation hole has been covered.


A56 Bat Volt Low: Battery voltage is low.


A57 Bat Cap Low: Battery capacity is low.


A59 Bat disconnect: Battery is disconnect.


A60 Overcharge: Charger voltage is high.


A61 Charger fail: Charger is failed.


A62 Bat Volt Low Or Bat Cap Low: Battery voltage is low, or Battery capacity is low.


A64 Over Load warning: UPS is overload.


A66 EPO Off: Missing the EPO connection.


A68 Over Temperature: High ambient temperature, or the ventilation hole has been covered. This is shown only when start up UPS.


A69 Fan Lock: fans can’t work because of lock.